Product Series


 

ISO 9001:2000
CONSORTIUM
MEMBER


Search for:


















 

TCS Series
Separate HEPA Filter & Blower Laminar Airflow
T-Grid HEPA filtration Ceiling System

Applications

Ceiling component filtration system for Cleanroom designs of
• Pharmaceutical Processing 
• Microelectronic Manufacturing
• Medical Device Manufacturing 
• Medical Operating Rooms

Specification (see details)

The system's flexibility provides protection of specific priority areas when a patterned ceiling coverage is specified. The system is designed to act as a HEPA filter source for Class 100 vertical laminar flow air when the building air system is not available.

System components are:
1. TFB: Remote T-Grid blower air handler with flexible duct.
2. TCD: T-Grid HEPA filter ceiling diffuser.

The blower unit can be suspended from the main ceiling or placed in a remote area. It can draw either ambient air from above the ceiling, or use inducted air supply. The duct connection size is1"dimt. Six feet of connection duct is provided per outlet. Blowers are designed in two versions:
One outlet: drives one HEPA filter at 800 CFM
Two outlets: drives two HEPA filter at 1600 CFM

The filter diffuser mounts onto a standard 2' x 4' suspended T-Grid ceiling, and because of its shallow length (only 24" is required for filter and duct connection), any low ceiling height can be converted into a cleanroom. The diffuser's HEPA filter is enclosed in an aluminum housing. Space and weight saving separators are used to create the Mini-pleat microglass fiber filter media pack that is sealed to the housing with a urethane bonding agent. The diffuser has two ports for DOP testing and air balancing.

Specifications

TFB Motor/Blower
TFB-1, one 10" outlet, 3/4 H.P., 800 CFM capacity.
TFB-2, two 10" outlet, 3/4" H.P., 1600 CFM capacity.
Six feet of connecting flexduct provided for each outlet
Eyebolts for ceiling suspension.
All electrical components are UL approved
150 Amps, 1PH.60 Hz junction box on for hard
wiring

TCD
Three inch mini-pleat media, aerosol challenged, zero-probed.
Minimum efficiency 99.99% at .3 microns
Aerosol challenger intake port
10" round duct intake port.
Internal damper plate.

Prefilter
1" bonded polyfiber media positioned at intake of motor/blower

Options Available Priced On Request

Extra 10" flexduct (up to 25')
Airflow control
ULPA filtration, .12 microns
Replacement prefilters, 12/case


Contact a qualified LM Air specialist about your specific needs

CLEANROOM & LAB EQUIPMENT MANUFACTURERS

 home co. profile  |  products / services  |  catalog  |  news / links  |  contact us


 

 

LM Air Technology, Inc. 1467 Pinewood St. Rahway, NJ. 07065   
E-mail:
sales@lmairtech.com    Tel: (732) 381-8200   Fax: (732) 381-4091  Toll free: (866) 381-8200